(E) Environment setting parameters
274
PARAMETERS
GOT initial setting (RS-485 terminals) (Pr.999 = "11, 13")
When Pr.414="1", the setting value is not changed.
• Initial setting with the GOT2000 series
- When "FREQROL 500/700/800, SENSORLESS SERVO" is selected for "Controller Type" in the GOT setting, set
Pr.999="11" to configure the GOT initial setting.
- When "FREQROL 800(Automatic Negotiation)" is selected for "Controller Type" in the GOT setting, the GOT automatic
connection can be used. When "FREQROL 800(Automatic Negotiation)" is selected for "Controller Type" in the GOT setting
and the GOT automatic connection is not used, set Pr.999="13" to configure the GOT initial setting. (Refer to page 595)
• Initial setting with the GOT1000 series
-Set Pr.999="11" to configure the GOT initial setting.
NOTE
• Always perform an inverter reset after the initial setting.
• For the details of connection with GOT, refer to the Instruction Manual of GOT.
Rated frequency (Pr.999 = "20 (50 Hz), 21 (60 Hz)")
Pr. Name
Initial
value
Pr.999="11" Pr.999="13" Refer to page
79 Operation mode selection
00 0 306
332 RS-485 communication speed
96 192 1152
563
333 RS-485 communication stop bit length
110 0
334 RS-485 communication parity check selection
21 1
335 RS-485 communication retry count
1 9999 9999
336 RS-485 communication check time interval
0 s 9999 9999
337 RS-485 communication waiting time setting
9999 0 ms 0 ms
340 Communication startup mode selection
01 1 315
341 RS-485 communication CR/LF selection
11 1 563
414 PLC function operation selection
0— 2 545
549 Protocol selection
00 0 579
Pr. Name
Initial value
Pr.999 = "21" Pr.999 = "20"
Refer to
page
FM type CA type
3 Base frequency
60 Hz 50 Hz 60 Hz 50 Hz 598
4 Multi-speed setting (high speed)
60 Hz 50 Hz 60 Hz 50 Hz 328
20
Acceleration/deceleration reference
frequency
60 Hz 50 Hz 60 Hz 50 Hz 285
37 Speed display
00 357
55 Frequency monitoring reference
60 Hz 50 Hz 60 Hz 50 Hz 369
66
Stall prevention operation reduction
starting frequency
60 Hz 50 Hz 60 Hz 50 Hz 348
116 Third output frequency detection
60 Hz 50 Hz 60 Hz 50 Hz 348
125 (903)
Terminal 2 frequency setting gain
frequency
60 Hz 50 Hz 60 Hz 50 Hz
415
126 (905)
Terminal 4 frequency setting gain
frequency
60 Hz 50 Hz 60 Hz 50 Hz
263 Subtraction starting frequency
60 Hz 50 Hz 60 Hz 50 Hz
540
266
Power failure deceleration time
switchover frequency
60 Hz 50 Hz 60 Hz 50 Hz
386 Frequency for maximum input pulse
60 Hz 50 Hz 60 Hz 50 Hz 324
505 Speed setting reference
60 Hz 50 Hz 60 Hz 50 Hz 357
808
Forward rotation speed limit/speed
limit
60 Hz 50 Hz 60 Hz 50 Hz 219
C14 (918) Terminal 1 gain frequency (speed)
60 Hz 50 Hz 60 Hz 50 Hz 415