(T) Multi-Function Input Terminal Parameters
PARAMETERS
409
5
GROUP
T
???????
Parameters referred to
Pr.22 Stall prevention operation level page 348
Pr.125 Terminal 2 frequency setting gain frequency, Pr.126 Terminal 4 frequency setting gain frequency page 415
Pr.252, Pr.253 override bias/gain page 411
Pr.561 PTC thermistor protection level page 331
Pr.858 Terminal 4 function assignment, Pr.868 Terminal 1 function assignment page 410
Running with analog input current
For constant pressure or temperature control with fans, pumps, or other
devices, automatic operation is available by setting the regulator output signal
4 to 20 mADC to between terminals 4 and 5.
To use the terminal 4, the AU signal needs to be turned ON.
Setting "6, 7, 16, or 17" in Pr.73 and turning the voltage/current input switches
ON sets terminal 2 to the current input specification. Concerning the settings,
the AU signal does not need to be turned ON.
Compensation input characteristics
when STF is ON
To perform forward/reverse rotation with the
analog input (polarity reversible operation)
Setting Pr.73 to a value of "10 to 17" enables the polarity reversible operation.
Setting ±input (0 to ±5 V or 0 to ±10 V) to the terminal 1 allows the operation of
forward/reverse rotation by the polarity.
STF
Inverter
Forward
rotation
Frequency
setting
SD
4
5
AU
Connection diagram using
terminal 4 (4 to 20mADC)
4 to 20mADC
Current
input
equipment
Voltage/current
input switch
2
4
STF
Inverter
Forward
rotation
SD
2
5
Connection diagram using
terminal 2 (4 to 20mADC)
Frequency
setting
4 to 20mADC
Current
input
equipment
Voltage/current
input switch
2
4
Forward
rotation
Reverse
rotation
Terminal 1 input (V)
+5
(+10)
-5
(-10)
0
60
Set frequency
(Hz)
Reversible
Not reversible