(A) Application parameters
520
PARAMETERS
Setting multiple PID pre-charge functions
• When the second pre-charge function is set, two sets of pre-charge functions can be switched for use. The second pre-
charge function is enabled by turning ON the RT signal.
• The second pre-charge function parameters and signals function in the same way as the following parameters and signals
of the first pre-charge function. Refer to the first pre-charge function when setting the second pre-charge functions.
NOTE
• The second PID pre-charge function is valid also when the first pre-charge function is set to invalid and the second pre-
charge function is set.
• When "10" (second function enabled only during constant-speed operation) is set to Pr.155, the second PID function is not
selected even if the RT signal turns ON.
Classification
First pre-charge function parameters Second pre-charge function parameters
Pr. Name Pr. Name
Parameter
760 Pre-charge fault selection 765 Second pre-charge fault selection
761 Pre-charge ending level 766 Second pre-charge ending level
762 Pre-charge ending time 767 Second pre-charge ending time
763 Pre-charge upper detection level 768
Second pre-charge upper detection
level
764 Pre-charge time limit 769 Second pre-charge time limit
Classification
First pre-charge function parameters Second pre-charge function parameters
Signal Name Signal Name
Input signal X77 Pre-charge end command X78 Second pre-charge end command
Output signal
Y49 During pre-charge operation Y50 During second pre-charge operation
Y51 Pre-charge time over Y52 Second pre-charge time over
Y53 Pre-charge level over Y54 Second pre-charge level over