Basic operation procedure (External operation)
BASIC OPERATION
113
4
NOTE
When both the forward rotation switch (STF) and the reverse rotation switch (STR) are ON, the motor cannot be started. If
both are turned ON while the inverter is running, the inverter decelerates to a stop.
Pr.178 STF terminal function selection must be set to "60" (or Pr.179 STR terminal function selection must be set to
"61"). (All are initial values.)
Setting Pr.79 Operation mode selection="3" also enables multi-speed operation.
If stopped using on the operation panel during the External operation, the inverter enters the PU stop status.
( appears on the operation panel.)
To reset the PU stop status, turn OFF the start switch (STF or STR), and then press . (Refer to page 260)
Parameters referred to
Pr.4 to Pr.6 (multi-speed setting) page 328
Pr.7 Acceleration time, Pr.8 Deceleration time page 285
Pr.178 STF terminal function selection page 430
Pr.179 STR terminal function selection page 430
Pr.79 Operation mode selection page 306