Parameter List
Parameter list (by parameter number)
PARAMETERS
129
Pr.
List
5
243 T041
Terminal 1 added compensation
amount (terminal 4)
0 to 100% 0.1% 75% 411
244 H100
Cooling fan operation selection 0, 1, 101 to 105 1 1 340
Slip
compensation
245 G203
Rated slip 0 to 50%, 9999 0.01% 9999 625
246 G204
Slip compensation time constant 0.01 to 10 s 0.01 s 0.5 s 625
247 G205
Constant-power range slip
compensation selection
0, 9999 1 9999 625
248 A006
Self power management selection 0 to 2 1 0 470
249 H101
Earth (ground) fault detection at
start
0, 1 1 0 341
250 G106
Stop selection
0 to 100 s,
1000 to 1100 s, 8888,
9999
0.1 s 9999 613
251 H200
Output phase loss protection
selection
0, 1 1 1 342
Frequency
compensation
function
252 T050
Override bias 0 to 200% 0.1% 50% 411
253 T051
Override gain 0 to 200% 0.1% 150% 411
254 A007
Main circuit power OFF waiting time 0 to 3600 s, 9999 1 s 600 s 470
Life check
255 E700
Life alarm status display (0 to 15) 1 0 278
256  E701
Inrush current limit circuit life
display
(0 to 100%) 1% 100% 278
257 E702
Control circuit capacitor life display (0 to 100%) 1% 100% 278
258  E703
Main circuit capacitor life display (0 to 100%) 1% 100% 278
259  E704
Main circuit capacitor life
measuring
0, 1 1 0 278
260 E602
PWM frequency automatic
switchover
0, 1 1 1 277
Power failure stop
261 A730
Power failure stop selection 0 to 2, 11, 12, 21, 22 1 0 540
262 A731
Subtracted frequency at
deceleration start
0 to 20 Hz 0.01 Hz 3 Hz 540
263 A732
Subtraction starting frequency 0 to 590 Hz, 9999 0.01 Hz 60 Hz 50 Hz 540
264 A733
Power-failure deceleration time 1 0 to 3600 s 0.1 s 5 s 540
265 A734
Power-failure deceleration time 2 0 to 3600 s, 9999 0.1 s 9999 540
266 A735
Power failure deceleration time
switchover frequency
0 to 590 Hz 0.01 Hz 60 Hz 50 Hz 540
267 T001
Terminal 4 input selection 0 to 2 1 0 406
268 M022
Monitor decimal digits selection 0, 1, 9999 1 9999 359
269 E023
Parameter for manufacturer setting. Do not set.
270 A200
Stop-on contact/load torque high-
speed frequency control selection
0 to 3, 11, 13 1 0
478,
481
Load torque
high speed
frequency control
271 A201
High-speed setting maximum
current
0 to 400% 0.1% 50% 481
272 A202
Middle-speed setting minimum
current
0 to 400% 0.1% 100% 481
273 A203
Current averaging range 0 to 590 Hz, 9999 0.01 Hz 9999 481
274 A204
Current averaging filter time
constant
1 to 4000 1 16 481
Stop-on
contact
control
275 A205
Stop-on contact excitation current
low-speed multiplying factor
50 to 300%, 9999 0.1% 9999 478
276 A206
PWM carrier frequency at stop-on
contact
0 to 9, 9999

19999478
0 to 4, 9999

Function
Pr.
Pr.
group
Name Setting range
Minimum
setting
increments
Initial value
Refer
to
page
Customer
setting
FM CA