(H) Protective function parameter
332
PARAMETERS
Electronic thermal O/L relay operation characteristic for induction motor
(Pr.9, E.THM)
• This function detects the overload (overheat) of the motor and trips the inverter by stopping the operation of the transistor at
the inverter output side.
• Set the rated current (A) of the motor in Pr.9. (If the motor has both 50 Hz and 60 Hz ratings and the Pr.3 Base frequency
is set to 60 Hz, set to 1.1 times the 60 Hz rated motor current.)
• Set "0" in Pr.9 to avoid activating the electronic thermal O/L relay function; for example, when using an external thermal
relay for the motor. (Note that the output transistor protection of the inverter is activated. (E.THT))
• When using the Mitsubishi constant-torque motor, set Pr.71 Applied motor = "1, 13 to 16, 50, 53, 54". (This will set a 100%
continuous torque characteristic in the low-speed range.)
When setting Pr.9 to a value (current value) of 50% of the inverter rated current
The % value denotes the percentage to the rated inverter current. It is not the percentage to the rated motor current.
When the electronic thermal O/L relay of the Mitsubishi constant-torque motor is set, the characteristic curve is as shown in this diagram at 6 Hz
or higher. (For selection of the operation characteristic , refer to page 438.)
Transistor protection is activated depending on the temperature of the heatsink. The protection may be activated even with less than 150%
depending on the operating conditions.
NOTE
• The internal accumulated heat value of the electronic thermal relay function is reset to the initial value by the inverter's power
reset and reset signal input. Avoid unnecessary reset and power-OFF.
• Install an external thermal relay (OCR) between the inverter and motors to operate several motors, a multi-pole motor or a
dedicated motor with one inverter. When setting an external thermal relay, note that the current indicated on the motor rating
plate is affected by the line-to-line leakage current. (Refer to page 82.) The cooling effect of the motor drops during low-speed
operation. Use a thermal protector or a motor with built-in thermistor.
• The protective characteristic of the electronic thermal O/L relay is degraded when there is a large difference in capacity
between the inverter and motor, and when the set value is small. In such case, use an external thermal relay.
• A dedicated motor cannot be protected by an electronic thermal O/L relay. Use an external thermal relay.
•Set Pr.9 = "0" for vector-control-dedicated motors (SF-V5RU) because they are equipped with thermal protectors.
• The transistor protection thermal O/L relay is activated early when the Pr.72 PWM frequency selection setting is increased.
52.5%
105%
50
100
150 230
60
120
180
240
50
60
70
6Hz
20Hz
10Hz
6Hz
0.5Hz
30Hz or more*
3
20Hz
10Hz
0.5Hz
Pr. 9 = 50% setting
of inverter rating*
1.2
Pr. 9 = 100% setting
of inverter rating*
1.2
(s) unit display in this region
(min) unit display in
this region
Operation time (min)Operation time (s)
Characteristic when
electronic thermal relay
function for motor
protection is turned off
(When Pr. 9 setting is 0(A))
30Hz
or more*
3
Inverter output power (%)
(% to the inverter rated current)
Operation region
Region on the right of
characteristic curve
Non-operation region
Region on the left of
Range for
the transistor
protection
*4