(M) Monitor display and monitor output signal
PARAMETERS
393
5
GROUP
M
Output frequency detection (FU (FB) signal, FU2 (FB2) signal, FU3 (FB3)
signal, Pr.42, Pr.43, Pr.50, Pr.116)
Output frequency detection (FU (FB)) is output when the output frequency reaches the Pr.42 setting or higher.
The FU (FU2, FU3) signals can be used for electromagnetic brake operation, opening, etc.
The FU (FU2, FU3) signal is output when the output frequency (frequency command) reaches the set frequency. The FB
(FU2, FU3) signal is output when the actual rotation detection speed (estimated speed in Real sensorless vector control,
feedback value in vector control) of the motor reaches the set frequency. The FU signal and FB signal are output in the
same manner under V/F control, Advanced magnetic flux vector control and encoder feedback control.
Frequency detection that is dedicated to reverse rotation can be set by setting the detection frequency in Pr.43. This is
useful for changing the timing of the electromagnetic brake operation during forward rotation (lifting) and reverse rotation
(lowering) in operations such as lift operation.
When Pr.43 "9999", forward rotation uses the Pr.42 setting and reverse rotation uses the Pr.43 setting.
When outputting a frequency detection signal separately from the FU signal, set the detection frequency in Pr.50 or Pr.116.
When the output frequency reaches the Pr.50 setting or higher, the FU2 (FB2) signal is output (when it reaches the Pr.116
setting or higher, the FU3 (FB3) signal is output).
For each signal, refer to the following table and assign the function by Pr.190 to Pr.196 (output terminal function
selection).
Pr.
Output
signal
Pr.190 to Pr.196 settings
Positive logic Negative logic
42, 43
FU 4 104
FB 41 141
50
FU2 5 105
FB2 42 142
116
FU3 6 106
FB3 43 143
Forward
rotation
Pr.116
Pr.50
Pr.42
Pr.43
Pr.50
Pr.116
OFFONOFFONOFF
Time
(Hz)
FU/FB
FU2/FB2
FU3/FB3
Output
signal
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
Output frequency
Reverse
rotation

Table of Contents