(M) Monitor display and monitor output signal
PARAMETERS
399
5
GROUP
M
NOTE
The output terminals that have not been assigned with a REM signal by Pr.190 to Pr.196 do not turn ON/OFF even if "0 or 1"
is set in the terminal bits of Pr.496 and Pr.497. (ON/OFF is performed with the assigned functions.)
When Pr.495 = "1 or 11" (remote output data retention at power OFF), take measures such as connecting R1/L11 with P/+,
and S1/L21 with N/- so that the control power is retained. If the control power is not retained, the output signal after turning
ON the power is not guaranteed to work. When connecting the high power factor converter (FR-HC2) or the converter unit
(FR-CC2), assign the instantaneous power failure detection (X11) signal to an input terminal to input the IPF signal from the
FR-HC2/FR-CC2 to the terminal for X11 signal.
???????
Parameters referred to
Pr.190 to Pr.196 (output terminal function selection) page 384