(C) Motor constant parameters
PARAMETERS
451
5
GROUP
C
Tuning the second applied motor
• When one inverter switches the operation between two different motors, set the second motor in Pr.450 Second applied
motor. (Refer to page 438.) In the initial setting, no second motor is applied.
• Turning ON the RT signal will enable the parameter settings for the second motor as shown below.
NOTE
• The RT signal is assigned to the terminal RT in the initial status. Set "3" in any of Pr.178 to Pr.189 (input terminal function
selection) to assign the RT signal to another terminal.
• Changing the terminal assignment using Pr.178 to Pr.189 (input terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Pr.1 Maximum frequency
Pr.9 Electronic thermal O/L relay page 331
Pr.31 to Pr.36 Frequency jump
Pr.71 Applied motor page 438
Pr.156 Stall prevention operation selection page 348
Pr.178 to Pr.189 (input terminal function selection) page 430
Pr.190 to Pr.196 (output terminal function selection) page 384
Pr.800 Control method selection page 164
Function RT signal ON (second motor) RT signal OFF (first motor)
Motor capacity Pr.453 Pr.80
Number of motor poles Pr.454 Pr.81
Motor excitation current Pr.455 Pr.82
Rated motor voltage Pr.456 Pr.83
Rated motor frequency Pr.457 Pr.84
Motor constant (R1) Pr.458 Pr.90
Motor constant (R2) Pr.459 Pr.91
Motor constant (L1)/d-axis
inductance (Ld)
Pr.460 Pr.92
Motor constant (L2)/q-axis
inductance (Lq)
Pr.461 Pr.93
Motor constant (X) Pr.462 Pr.94
Auto tuning setting/status Pr.463 Pr.96
Frequency search gain Pr.560 Pr.298