(C) Motor constant parameters
PARAMETERS
457
5
GROUP
C
When offline auto tuning ends, press on the operation panel during PU operation. For External operation, turn OFF
the start signal (STF signal or STR signal).
This operation resets the offline auto tuning, and the PU's monitor display returns to the normal indication.
(Without this operation, next operation cannot be started.)
NOTE
The motor constants measured once in the offline auto tuning are stored as parameters and their data are held until the
offline auto tuning is performed again. However, the tuning data is cleared by performing all parameter clear.
Changing Pr.71 after tuning completion will change the motor constant. For example, if Pr.71 = "8093" is set after tuning is
performed with Pr.71 ="8090", the tuning data becomes invalid. Set Pr.71 = "8090" again for using the tuning data.
If offline auto tuning has ended in error (see the table below), motor constants are not set.
Perform an inverter reset and restart tuning.
When tuning is ended forcibly by pressing or turning OFF the start signal (STF or STR) during tuning, offline auto
tuning does not end properly. (The motor constants have not been set.)
Perform an inverter reset and restart tuning.
NOTE
An instantaneous power failure occurring during tuning will result in a tuning error.
After power is restored, the inverter starts normal operation. Therefore, when STF (STR) signal is ON, the motor runs in the
forward (reverse) rotation.
Any alarm occurring during tuning is handled as in the normal operation. However, if the retry function is set, no retry is
performed even when a protective function that performs a retry is activated.
The set frequency monitor displayed during the offline auto tuning is 0 Hz.
Error display Error cause Countermeasures
8 Forced end Set Pr.96 (Pr.463) = "1" or "11" and try again.
9 Inverter protective function operation Make the setting again.
92
The converter output voltage has dropped to
75% of the rated voltage.
Check for the power supply voltage fluctuation.
Check the Pr.84 Rated motor frequency setting.
93
Calculation error.
The motor is not connected.
Check the motor wiring and make the setting again.
94
Rotation tuning frequency setting error
(The frequency command for the tuning was
given to exceed the maximum frequency
setting, or to be in the frequency jump range.)
Check the Pr.1 Maximum frequency and Pr.31 to
Pr.36 Frequency jump settings.
Caution
Note that the motor may start running suddenly.