(A) Application parameters
548
PARAMETERS
Operation outline
This function samples the status (analog monitor and digital monitor) of the inverter, traces the sampling data when a
trigger (trace start condition) is generated, and saves the resulting trace data.
When the trace function is set enabled, samplings are collected and the inverter goes into the pre-trigger status.
In the pre-trigger status, samples are collected, and the trigger standby status is entered when sufficient samples for the
number of pre-trigger samples have been collected.
When the trigger is generated in the trigger standby status, the trace is started and the trace data is saved.
1036
A919
Analog trigger operation
selection
0
0
Sampling starts when the value of the analog monitor exceeds
the value set at the trigger level (Pr.1037)
1
Sampling starts when the value of the analog monitor falls
below the value set at the trigger level (Pr.1037)
1037
A920
Analog trigger level
1000 600 to 1400
Set the level at which the analog trigger turns ON.
The trigger level is the value obtained by subtracting 1000
from the set value.
1038
A930
Digital source selection
(1ch)
1
1 to 255
Select the digital data (I/O signal) to be sampled on each
channel.
1039
A931
Digital source selection
(2ch)
2
1040
A932
Digital source selection
(3ch)
3
1041
A933
Digital source selection
(4ch)
4
1042
A934
Digital source selection
(5ch)
5
1043
A935
Digital source selection
(6ch)
6
1044
A936
Digital source selection
(7ch)
7
1045
A937
Digital source selection
(8ch)
8
1046
A938
Digital trigger channel
1 1 to 8 Select the digital channel to be the trigger.
1047
A939
Digital trigger operation
selection
0
0 Trace starts when the signal turns ON
1 Trace starts when the signal turns OFF
Pr. Name
Initial
value
Setting
range
Description
Sampling start
Sampling start
Sampling data
0% 90%
Pre-trigger sampling number
If the data is short for the pre-trigger sampling,
the inverter goes into the pre-trigger state.
Sampling data
0% 90% 100%
Pre-trigger sampling number
Once the enough data is collected for trigger sampling,
the inverter goes into the trigger-ready state.
Data in the period
is discarded.
Data in the period
is discarded.
Sampling start
Sampling data
0% 90% 100%
A trigger occurs Trace completed
Trace start
At trigger generation, samples equivalent to the 100%
pre-trigger sampling number are collected and saved.