Causes and corrective actions
646
PROTECTIVE FUNCTIONS
Operation panel
indication
Er8
Name
USB memory device operation error
Description
An operation command was given during the USB memory device operation.
A copy operation (writing) was performed while the PLC function was in the RUN state.
A copy operation was attempted for a password locked project.
Check point
Check if the USB memory device is operating.
Check if the PLC function is in the RUN state.
Check if the project data is locked with a password.
Corrective action
Perform the operation after the USB memory device operation is completed.
Stop the PLC function. (Refer to page 547 and the PLC function programming manual.)
Unlock the password of the project data using FR Configurator2. (Refer to the Instruction Manuals of FR
Configurator2 and GX Works2.)
Operation panel
indication
rE1
Name
Parameter read error
Description
A failure has occurred at the operation panel side EEPROM while reading the copied parameters.
A failure has occurred in the USB memory device while copying the parameters or reading the PLC function
project data.
Check point
————
Corrective action
Perform parameter copy again. (Refer to page 632, page 635.)
Perform PLC function project data copy again.(Refer to page 547)
The USB memory device may be faulty. Replace the USB memory device.
The operation panel (FR-DU08) may be faulty. Please contact your sales representative.
Operation panel
indication
rE2
Name
Parameter write error
Description
Parameter copy from the operation panel to the inverter was attempted during operation.
A failure has occurred at the operation panel side EEPROM while writing the copied parameters.
A failure has occurred in the USB memory device while writing the copied parameters or PLC function
project data.
Check point
Check that the inverter is stopped.
Corrective action
After stopping the operation, perform parameter copy again. (Refer to page 632.)
The operation panel (FR-DU08) may be faulty. Please contact your sales representative.
Perform parameter copy or PLC project data copy again. (Refer to page 547 and page 635)
The USB memory device may be faulty. Replace the USB memory device.
Operation panel
indication
rE3
Name
Parameter verification error
Description
The data in the inverter are different from the data in the operation panel.
A failure has occurred at the operation panel side EEPROM during parameter verification.
A failure has occurred in the USB memory device during parameter verification.
The data in the inverter are different from the data in the USB memory device or the personal computer (FR
Configurator2)
Check point
Check the parameter setting of the source inverter against the setting of the destination inverter.
Corrective action
Continue the verification by pressing .
Perform parameter verification again. (Refer to page 634.)
The operation panel (FR-DU08) may be faulty. Please contact your sales representative.
The USB memory device may be faulty. Replace the USB memory device.
Verify the PLC function project data again.(Refer to page 547.)