Chapter 5 Trial operation and Tuning ASDA-A2
5-16 Revision February, 2017
5.6.5 Limit of Inertia Ratio
Acceleration / Deceleration time of reaching 2000 r/min should be less than 1 second.
The speed in forward and reverse direction should be higher than 200 r/min.
The load inertia should be under 100 times of motor inertia.
The change of external force of inertia ratio cannot be too severe.
In auto mode, the inertia value will be saved to P1-37 every 30 minutes; while in semi-auto mode,
the inertia value will be saved to P1-37 only until the system inertia is stable and stops the
estimation of load inertia.

Table of Contents

Other manuals for Delta ASDA-A2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ASDA-A2 and is the answer not in the manual?

Delta ASDA-A2 Specifications

General IconGeneral
Control ModePosition, Speed, Torque
ModelASDA-A2 Series
Operating Voltage200 ~ 230VAC / 380 ~ 480VAC
Power Supply200-230VAC ±10%, single-phase
Communication InterfaceRS-485, CANopen
FeedbackIncremental encoder, Absolute encoder
ProtectionOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
Operating Temperature0°C
Storage Temperature-20°C
Humidity20% to 90% RH (non-condensing)
Position Control Mode FeaturesElectronic Cam
WeightVaries depending on the model. Please refer to the specific model's datasheet.