ASDA-A2 Chapter 8 Parameters
Revision February, 2017 8-83
Y: Initial position setting
0: After servo on, the motor will regard the current position as the
position when the voltage is 0. Then the motor will operate to the
position according to the command issued by analog input.
1: After SERVO ON, if the command level is not changed, the motor
will not operate. The position the motor stops is the position that
corresponds to the current command level.
Motor position
(Turn)
Analog input
command
(V)
Command
level
The current
position of the
motor
The position which
corresponds to 0V
remains
When executing this
function, if the
command level is not
changed, the motor
will not operate
Z: Reserved
U: Reserved
NOTE
Version after firmware v1.031 sub8 supports this function.
P1-65 Smooth Constant of Analog Position Command
Address: 0182H
0183H
Operational
Interface:
Panel/Software Communication
Related Section: N/A
Default:
1
Control
Mode:
PT
Unit:
10 ms
Motor position
Analog
input
command
(V)
Current
command
level
See the current
position as the
position when
voltage is 0
When executing
this function, the
motor will operate
to the position
which corresponds
to the current
voltage command
(Turn)