Chapter 8 Parameters ASDA-A2
8-76 Revision February, 2017
Format:
DEC
Settings:
In speed mode, when the deviation value between speed command
and motor feedback speed is smaller than the range set by P1-47
and reaches the time set by P1-79, DO.SP_OK will be On. If the
deviation value exceeds the range set by P1-47, it has to reclock the
time.
P1-50 ~
P1-51
Reserved
P1-52 RES1 Regenerative Resistor Value
Address: 0168H
0169H
Operational
Interface:
Panel / Software Communication
Related Section:
2.7
Default:
Determined by the model. Please refer to the
following table.
Control
Mode:
ALL
Unit:
Ohm
Range:
220V
Model
Setting
Range
400W (included) or
below
30 ~ 750
750W ~ 1.5kW 20 ~ 750
2kW ~ 4.5kW 10 ~ 750
5.5
W 8 ~ 750
7.5kW 5 ~ 750
11kW 8 ~ 750
15 kW 5 ~ 750
400V
Model
Setting
Range
750W ~ 1.5kW 60 ~ 750
1.5kW ~ 2kW 40 ~ 750
3
W 30 ~ 750
4.5kW ~ 5.5kW 20 ~ 750
7.5kW 15 ~ 750
Data Size:
16-bit
Format:
Decimal