ASDA-A2 Chapter 8 Parameters
Revision February, 2017 8-65
P1-31 Reserved
P1-32 LSTP Motor Stop Mode
Address: 0140H
0141H
Operational
Interface
Panel / Software Communication
Related Section: -
Default
0
Control
Mode
ALL
Unit
-
Range
0 ~ 0x20
Data Size
16-bit
Format
Hexadecimal
Settings
Not in use
Selection of executing dynamic brake
Not in use
Selection of executing dynamic brake: Stop Mode when Servo Off or
Alarm (including EMGS) occurs.
0: Execute dynamic brake
1: Motor free run
2: Execute dynamic brake first, then execute free run until it stops
(The motor speed is slower than P1-38).
When PL and NL occur, please refer to event time setting value of P5-
03 for determining the deceleration time. If the setting is 1 ms, it can
stop instantaneously.