Chapter 8 Parameters ASDA-A2
8-94 Revision February, 2017
P2-06 KVI Speed Integral Compensation
Address: 020CH
020DH
Operational
Interface
Panel / Software Communication
Related Section:
6.3.6
Default
100
Control
Mode
ALL
Unit
rad/s
Range
0 ~ 1023
Data Size
16-bit
Format
Decimal
Settings
Increasing the value of speed integral compensation can enhance
speed response and diminish the deviation of speed control. However,
if the value is set too big, it would easily cause resonance and noise.
P2-07 KVF Speed Feed Forward Gain
Address: 020EH
020FH
Operational
Interface
Panel / Software Communication
Related Section:
6.3.6
Default
0
Control
Mode
ALL
Unit
%
Range
0 ~ 100
Data Size
16-bit
Format
Decimal
Settings
When the speed control command runs smoothly, increasing the gain
value can reduce the speed command error. If the command does not
run smoothly, decreasing the gain value can reduce the mechanical
vibration during operation.

Table of Contents

Other manuals for Delta ASDA-A2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ASDA-A2 and is the answer not in the manual?

Delta ASDA-A2 Specifications

General IconGeneral
Control ModePosition, Speed, Torque
ModelASDA-A2 Series
Operating Voltage200 ~ 230VAC / 380 ~ 480VAC
Power Supply200-230VAC ±10%, single-phase
Communication InterfaceRS-485, CANopen
FeedbackIncremental encoder, Absolute encoder
ProtectionOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
Operating Temperature0°C
Storage Temperature-20°C
Humidity20% to 90% RH (non-condensing)
Position Control Mode FeaturesElectronic Cam
WeightVaries depending on the model. Please refer to the specific model's datasheet.

Related product manuals