EasyManuals Logo
Home>IDEC>Organizer>WindO/I-NV4

IDEC WindO/I-NV4 User Manual

IDEC WindO/I-NV4
1738 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #1510 background imageLoading...
Page #1510 background image
3 File Copy Function
29-38 WindO/I-NV4 User’s Manual
3.5 Precautions
• When the MICRO/I is under the Run Mode, the maximum size per single file that can be read or written with the
File Copy function is 256 MB.
• Access to the file being copied is not allowed while the file copy function is running. Therefore, data may be
missing when copying files used by the running project such as log data. When copying a file used by the running
project, use File Manager on the MICRO/I under the System Mode.
• While running the file copy function using a Key Button, Multi-Button, or Multi-Command, if a data transfer function
(project transfer, PLC program transfer, or file copy) is initiated, the only function that will work is the currently
running function. If two or more data transfer functions are configured to a Multi-Button or Multi-Command, only
the data transfer function displayed at the top of the function list on the parts property dialog box is run.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC WindO/I-NV4 and is the answer not in the manual?

IDEC WindO/I-NV4 Specifications

General IconGeneral
BrandIDEC
ModelWindO/I-NV4
CategoryOrganizer
LanguageEnglish