Parameter List
Parameter list (by parameter number)
PARAMETERS
127
Pr.
List
5
Current detection
148 H620
Stall prevention level at 0 V input 0 to 400% 0.1% 150% 348
149 H621
Stall prevention level at 10 V input 0 to 400% 0.1% 200% 348
150 M460
Output current detection level 0 to 400% 0.1% 150% 395
151 M461
Output current detection signal
delay time
0 to 10 s 0.1 s 0 s 395
152 M462
Zero current detection level 0 to 400% 0.1% 5% 395
153 M463
Zero current detection time 0 to 10 s 0.01 s 0.5 s 395
154 H631
Voltage reduction selection during
stall prevention operation
0, 1, 10, 11 1 1 348
155 T730
RT signal function validity
condition selection
0, 10 1 0 434
156 H501
Stall prevention operation selection 0 to 31, 100, 101 1 0 348
157 M430
OL signal output timer 0 to 25 s, 9999 0.1 s 0 s
185,
348
158 M301
AM terminal function selection
1 to 3, 5 to 14, 17, 18,
21, 24, 32 to 34, 50,
52 to 54, 61, 62, 67,
70, 87 to 90, 91 to 98
11 369
159 A005
Automatic switchover frequency
range from bypass to inverter
operation
0 to 10 Hz, 9999 0.01 Hz 9999 464
160 E440
User group read selection
0, 1, 9999 1 0 275
161 E200
Frequency setting/key lock
operation selection
0, 1, 10, 11 1 0 263
Automatic
restart
functions
162 A700
Automatic restart after
instantaneous power failure
selection
0 to 3, 10 to 13 1 0
528,
534,
536
163 A704
First cushion time for restart 0 to 20 s 0.1 s 0 s 528
164 A705
First cushion voltage for restart 0 to 100% 0.1% 0% 528
165 A710
Stall prevention operation level for
restart
0 to 400% 0.1% 150% 528
Current
detection
166 M433
Output current detection signal
retention time
0 to 10 s, 9999 0.1 s 0.1 s 395
167 M464
Output current detection operation
selection
0, 1, 10, 11 1 0 395
168
E000
Parameter for manufacturer setting. Do not set.
E080
169
E001
E081
Cumulative
monitor
clear
170 M020
Watt-hour meter clear 0, 10, 9999 1 9999 359
171 M030
Operation hour meter clear 0, 9999 1 9999 359
User
group
172 E441
User group registered display/
batch clear
9999, (0 to 16) 1 0 275
173 E442
User group registration 0 to 1999, 9999 1 9999 275
174 E443
User group clear 0 to 1999, 9999 1 9999 275
Function
Pr.
Pr.
group
Name Setting range
Minimum
setting
increments
Initial value
Refer
to
page
Customer
setting
FM CA
Simple
Simple
Simple

Table of Contents