Parameter List
Parameter list (by parameter number)
126
PARAMETERS
PU connector communication
117 N020
PU communication station number 0 to 31 1 0 563
118 N021
PU communication speed
48, 96, 192, 384, 576,
768, 1152
1 192 563
119
-
PU communication stop bit length /
data length
0, 1, 10, 11
1
1
563
N022
PU communication data length 0, 1 0
N023
PU communication stop bit length 0, 1 1
120 N024
PU communication parity check 0 to 2 1 2 563
121 N025
Number of PU communication
retries
0 to 10, 9999 1 1 563
122 N026
PU communication check time
interval
0, 0.1 to 999.8 s, 9999 0.1 s 9999 563
123 N027
PU communication waiting time
setting
0 to 150 ms, 9999 1 ms 9999 563
124 N028
PU communication CR/LF selection 0 to 2 1 1 563
125 T022
Terminal 2 frequency setting gain
frequency
0 to 590 Hz 0.01 Hz 60 Hz 50 Hz 415
126 T042
Terminal 4 frequency setting gain
frequency
0 to 590 Hz 0.01 Hz 60 Hz 50 Hz 415
PID operation
127 A612
PID control automatic switchover
frequency
0 to 590 Hz, 9999 0.01 Hz 9999 501
128 A610
PID action selection
0, 10, 11, 20, 21,
40 to 43, 50, 51, 60,
61, 70, 71, 80, 81, 90,
91, 100, 101, 1000,
1001, 1010, 1011,
2000, 2001, 2010,
2011
10
501,
521
129 A613
PID proportional band 0.1 to 1000%, 9999 0.1% 100%
501,
521
130 A614
PID integral time 0.1 to 3600 s, 9999 0.1 s 1 s
501,
521
131 A601
PID upper limit 0 to 100%, 9999 0.1% 9999
501,
521
132 A602
PID lower limit 0 to 100%, 9999 0.1% 9999
501,
521
133 A611
PID action set point 0 to 100%, 9999 0.01% 9999
501,
521
134 A615
PID differential time 0.01 to 10 s, 9999 0.01 s 9999
501,
521
Bypass
135 A000
Electronic bypass sequence
selection
0, 1 1 0 464
136 A001
MC switchover interlock time 0 to 100 s 0.1 s 1 s 464
137 A002
Start waiting time 0 to 100 s 0.1 s 0.5 s 464
138 A003
Bypass selection at a fault 0, 1 1 0 464
139 A004
Automatic switchover frequency
from inverter to bypass operation
0 to 60 Hz, 9999 0.01 Hz 9999 464
Backlash
measures
140 F200
Backlash acceleration stopping
frequency
0 to 590 Hz 0.01 Hz 1 Hz 290
141 F201
Backlash acceleration stopping
time
0 to 360 s 0.1 s 0.5 s 290
142 F202
Backlash deceleration stopping
frequency
0 to 590 Hz 0.01 Hz 1 Hz 290
143 F203
Backlash deceleration stopping
time
0 to 360 s 0.1 s 0.5 s 290
144 M002
Speed setting switchover
0, 2, 4, 6, 8, 10, 12,
102, 104, 106, 108,
110, 112
14 357
PU
145 E103
PU display language selection 0 to 7 1 1 261
147 F022
Acceleration/deceleration time
switching frequency
0 to 590 Hz, 9999 0.01 Hz 9999 285
Function
Pr.
Pr.
group
Name Setting range
Minimum
setting
increments
Initial value
Refer
to
page
Customer
setting
FM CA
Simple
Simple
Simple
Simple