Parameter List
Parameter list (by parameter number)
144
PARAMETERS
1115 G218
Speed control integral term clear
time
0 to 9998 ms 1 ms 0 s 192
1116 G206
Constant output range speed
control P gain compensation
0 to 100% 0.1% 0% 192
1117 G261
Speed control P gain 1 (per-unit
system)
0 to 300, 9999 0.01 9999 192
1118 G361
Speed control P gain 2 (per-unit
system)
0 to 300, 9999 0.01 9999 192
1119 G262
Model speed control gain (per-unit
system)
0 to 300, 9999 0.01 9999 200
1121 G260
Per-unit speed control reference
frequency
0 to 400 Hz 0.01 Hz
120 Hz
192
60 Hz
PID control
1134 A605
PID upper limit manipulated value 0 to 100% 0.1% 100% 521
1135 A606
PID lower limit manipulated value 0 to 100% 0.1% 100% 521
1136 A670
Second PID display bias coefficient 0 to 500, 9999 0.01 9999 514
1137 A671
Second PID display bias analog
value
0 to 300% 0.1% 20% 514
1138 A672
Second PID display gain coefficient 0 to 500, 9999 0.01 9999 514
1139 A673
Second PID display gain analog
value
0 to 300% 0.1% 100% 514
1140 A664
Second PID set point/deviation
input selection
1 to 5 1 2 501
1141 A665
Second PID measured value input
selection
1 to 5 1 3 501
1142 A640
Second PID unit selection 0 to 43, 9999 1 9999 501
1143 A641
Second PID upper limit 0 to 100%, 9999 0.1% 9999 501
1144 A642
Second PID lower limit 0 to 100%, 9999 0.1% 9999 501
1145 A643
Second PID deviation limit 0 to 100%, 9999 0.1% 9999 501
1146 A644
Second PID signal operation
selection
0 to 3, 10 to 13 1 0 501
1147 A661
Second output interruption
detection time
0 to 3600 s, 9999 0.1 s 1 501
1148 A662
Second output interruption
detection level
0 to 590 Hz 0.01 Hz 0 Hz 501
1149 A663
Second output interruption cancel
level
900 to 1100% 0.1% 1000% 501
PLC
function
1150
to
1199
A810
to
A859
PLC function user parameters 1 to
50
0 to 65535 1 0 545
1220 B100
Target position/speed selection 0 to 2 1 0 731
Simple position control
1221 B101
Start command edge detection
selection
0, 1 1 0 232
1222 B120
First positioning acceleration time 0.01 to 360 s 0.01 s 5 s 232
1223 B121
First positioning deceleration time 0.01 to 360 s 0.01 s 5 s 232
1224 B122
First positioning dwell time 0 to 20000 ms 1 ms 0 ms 232
1225 B123
First positioning sub-function
0, 1, 10, 11, 100, 101,
110, 111
110 232
1226 B124
Second positioning acceleration
time
0.01 to 360 s 0.01 s 5 s 232
1227 B125
Second positioning deceleration
time
0.01 to 360 s 0.01 s 5 s 232
1228 B126
Second positioning dwell time 0 to 20000 ms 1 ms 0 ms 232
1229 B127
Second positioning sub-function
0, 1, 10, 11, 100, 101,
110, 111
110 232
1230 B128
Third positioning acceleration time 0.01 to 360 s 0.01 s 5 s 232
1231 B129
Third positioning deceleration time 0.01 to 360 s 0.01 s 5 s 232
Function
Pr.
Pr.
group
Name Setting range
Minimum
setting
increments
Initial value
Refer
to
page
Customer
setting
FM CA