(A) Application parameters
PARAMETERS
505
5
GROUP
A
Connection diagram
Selection of deviation value, measured value and set point input method,
and PID action method (Pr.128, Pr.609, Pr.610)
Using Pr.128, select the input method for the PID set point, measured value detected by the meter, and externally
calculated deviation. Also, select forward or reverse action.
Switch the power voltage/current specifications of terminals 2 and 4 by Pr.73 Analog input selection or Pr.267 Terminal 4
input selection to match the specification of the input device. After changing the Pr.73 and Pr.267 settings, check the
voltage/current input selection switch. Incorrect setting may cause a fault, failure or malfunction. (Refer to page 406 for the
setting.)
Sink logic
Pr.128=20
Pr.183=14
Pr.191=47
Pr.192=16
Pr.193=14
Pr.194=15
 Prepare a power supply matched to the power supply specification of the detector.
 The output signal terminal to be used differs according to the Pr.190 to Pr.196 (output terminal function selection) setting.
 The input signal terminal to be used differs according to the Pr.178 to Pr.189 (input terminal function selection) setting.
 The AU signal need not be input.
Pr.128
setting
Pr.609
Pr.610
PID action Set point input Measured value input Deviation input
0
Invalid
PID invalid - - -
10 Reverse action
- - Terminal 1
11 Forward action
20 Reverse action
Terminal 2 or Pr.133
 Terminal 4 -
21 Forward action
40 to 43 Valid Dancer control For details on dancer control, refer to page 521
50
Invalid
Reverse action
- - CC-Link communication

51 Forward action
60 Reverse action
CC-Link communication
 CC-Link communication -
61 Forward action
70 Reverse action
--
PLC function
(with frequency reflected)
71 Forward action
80 Reverse action
PLC function
(with frequency reflected)

PLC function
(with frequency reflected)

-
81 Forward action
90 Reverse action
--
PLC function
(without frequency
reflected)

91 Forward action
100 Reverse action PLC function
(without frequency
reflected)

PLC function
(without frequency
reflected)

-
101 Forward action
Power supply
MCCB
Inverter
Forward
rotation
Reverse
rotation
PID control
selection
Setting
Potentiometer
(Set point setting)
0 24V
Power
supply
∗1
AC1φ
200/220V 50/60Hz
R/L1
S/L2
T/L3
STF
STR
RT(X14)
∗3
SD
10
2
5
4
U
V
W
∗2(FUP)FU
∗2(FDN)OL
SE
(Measured value) 4 to 20mA
Motor
M
Pump
P
Upper limit
∗2(PID)SU
During PID action
Lower limit
Output signal common
2-wire type
Detector
3-wire
type
+
-
(24V)
∗2(RL)IPF
1
(COM)
Forward rotation
output
Reverse rotation
output
-
++
(OUT)
∗4