EasyManua.ls Logo

Mitsubishi FR-A800

Mitsubishi FR-A800
746 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
(A) Application parameters
506
PARAMETERS
 When Pr.133 "9999", the Pr.133 setting is valid.
 For the details of CC-Link communication, refer to the Instruction Manual of the option FR-A8NC, FR-A8NCE.
 For the details of the PLC function, refer to the PLC Function Programming Manual.
The set point/deviation input method can also be flexibly selected by Pr.609 PID set point/deviation input selection and
the measured value input method can be selected by Pr.610 PID measured value input selection. Selection by Pr.609
and Pr.610 is valid when Pr.128 = "1000 to 2011".
 When the same input method has been selected for the set point and measured value using Pr.609 and Pr.610, set point input is invalid. (The
inverter runs at set point 0%)
NOTE
When terminals 2 and 4 are selected for deviation input, perform bias calibration using C3 and C6 to prevent a minus voltage
from being entered as the deviation input signal. Input of a minus voltage might damage devices and the inverter.
The following shows the relationship between the input values of the analog input terminals and set point, measured value
and deviation. (Calibration parameter initial values)
 Can be changed by Pr.73 and Pr.267 and the voltage/current input switch. (Refer to page 406.)
NOTE
Always perform calibration after changing the voltage/input specification with Pr.73, Pr.267, and the voltage/current input
selection switch.
1000
Valid
Reverse action
According to Pr.609
 According to Pr.610 -
1001 Forward action
1010 Reverse action
- - According to Pr.609
1011 Forward action
2000
Reverse action (without
frequency reflected)
According to Pr.609
 According to Pr.610 -
2001
Forward action (without
frequency reflected)
2010
Reverse action (without
frequency reflected)
- -- According to Pr.609
2011
Forward action (without
frequency reflected)
Pr.609 and
Pr.610 settings
Input method
1 Terminal 1
2 Terminal 2
3 Terminal 4
4 CC-Link communication
5 PLC function
Input
terminal
Inspect
specification

Relationship with analog input
Calibration parameter
Set point Result Deviation
Terminal 2
0 to 5 V
0 V=0%
5 V=100%
0 V=0%
5 V=100%
0 V=0%
5 V=100%
Pr.125, C2 to C40 to 10 V
0 V=0%
10 V=100%
0 V=0%
10 V=100%
0 V=0%
10 V=100%
0 to 20 mA
0 mA=0%
20 mA=100%
0 mA=0%
20 mA=100%
0 V=0%
20 mA=100%
Terminal 1
0 to 5 V
-5 V to 0 V=0%
5 V=+100%
-5 V to 0 V=0%
5 V=+100%
-5 V=-100%
0 V=0%
5 V=+100%
When Pr.128 = "10",
Pr.125, C2 to C4.
When Pr.128 "1000",
C12 to C15.
0 to 10 V
-10 V to 0 V=0%
10 V=+100%
-10 V to 0 V=0%
10 V=+100%
-10 V=-100%
0 V=0%
10 V=+100%
Terminal 4
0 to 5 V
0 V to 1 V=0%
5 V=100%
0 Vto 1 V=0%
5 V=100%
0 V=-20%
1 V=0%
5 V=100%
Pr.126, C5 to C70 to 10 V
0 V to 2 V=0%
10 V=100%
0 V to 2 V=0%
10 V=100%
0 V=-20%
1 V=0%
10 V=100%
0 to 20 mA
0 to 4 mA=0%
20 mA=100%
0 to 4 mA=0%
20 mA=100%
0 V=-20%
4 mA=0%
20 mA=100%
Pr.128
setting
Pr.609
Pr.610
PID action Set point input Measured value input Deviation input

Table of Contents

Related product manuals