(N) Operation via communication and its settings
564
PARAMETERS
[Parameters related to communication with the RS-485 terminals]
NOTE
The monitored items and parameter settings can be read during communication with the Pr.336 RS-485 communication
check time interval = "0 (initial value)" setting, but such operation will become faulty once the operation mode is changed to
the NET operation mode. When the NET operation mode is selected as the start-up operation mode, communication is
performed once, then a Communication fault (inverter) (E.SER) occurs. To perform operation or parameter writing via
communication, set "9999" or a large setting value in Pr.336. (The setting value is determined by the computer
program.)(Refer to
page 571.)
Always reset the inverter after making the initial settings of the parameters. After changing the communication-related
parameters, communication cannot be made until the inverter is reset.
Parameter
number
Name
Initial
value
Setting
range
Description
331
N030
RS-485
communication station
number
0
0 to 31
(0 to 247)

Set the inverter station number. (Same specifications as
Pr.117)
332
N031
RS-485
communication speed
96
3, 6, 12, 24,
48, 96, 192,
384, 576, 768,
1152
Select the communication speed. (Same specifications as
Pr.118)
N032
RS-485
communication data
length
0 0, 1 Select the data length. (Same specifications as P.E022)
N033
RS-485
communication stop
bit length
1 0, 1 Select the stop bit length. (Same specifications as P.E023)
333
RS-485
communication stop
bit length / data length
1 0, 1, 10, 11
Select the stop bit length and data bit length. (Same
specifications as Pr.119)

334
N034
RS-485
communication parity
check selection
2 0, 1, 2
Select the parity check specifications. (Same specifications as
Pr.120)
335
N035
RS-485
communication retry
count
1 0 to 10, 9999
Set the permissible number of retries for unsuccessful data
reception. (Same specifications as Pr.121)
336
N036

RS-485
communication check
time interval
0 s
0
RS-485 communication is available, but the inverter trips in the
NET operation mode.
0.1 to 999.8 s
Set the interval of the communication check (signal loss
detection) time. (Same specifications as Pr.122)
9999 No communication check (signal loss detection)
337
N037

RS-485
communication
waiting time setting
9999
0 to 150 ms,
9999
Set the waiting time between data transmission to the inverter
and the response. (Same specifications as Pr.123)
341
N038
RS-485
communication CR/LF
selection
1 0, 1, 2
Select the presence/absence of CR/LF. (Same specifications as
Pr.124)
 When "1" (Modbus-RTU protocol) is set in Pr.549, the setting range within parentheses is applied.
 When a value outside the setting range is set, the inverter operates at the initial value.
 In the Modbus-RTU protocol, the data length is fixed at 8 bits.
 In the Modbus-RTU protocol, Pr.334 setting is applied as the stop bit length. (Refer to page 579.)
 In the Modbus-RTU protocol, this is invalid.