(N) Operation via communication and its settings
PARAMETERS
567
5
GROUP
N
• Data reading format
a. Communication request data from the computer to the inverter
c. Reply data from the inverter to the computer (No data error detected)
c. Reply data from the inverter to the computer (Data error detected)
e. Transmission data from the computer to the inverter when reading data
Indicates a control code.
Specifies the inverter station numbers in the range of H00 to H1F (stations 0 to 31) in hexadecimal.
When Pr.123 or Pr.337 (Waiting time setting) 9999, create a communication request data without "waiting time" in the data format. (The
number of characters decreases by 1.)
CR, LF code: When data is transmitted from the computer to the inverter, codes CR (carriage return) and LF (line feed) are automatically set at
the end of a data group on some computers. In this case, setting must be also made on the inverter according to the computer. Whether the CR
and LF codes will be present or absent can be selected using Pr.124 or Pr.341 (CR/LF selection).
Format
Number of characters
1 2 3 4 5 6 7 8 9
B
ENQ
Inverter station
No.
Instruction
code
Sum check
Format
Number of characters
1 2 3 4 5 6 7 8 9 10 11 12 13
ESTX
Inverter station
No.
Read data ETX Sum check
E1 STX
Inverter station
No.
Read data ETX Sum check
E2 STX
Inverter station
No.
Read data ETX Sum check
Format
Number of characters
1 2 3 4 to 23 24 25 26 27
E3 STX
Inverter station
No.
Read data (Inverter model information) ETX Sum check
Format
Number of characters
1 2 3 4 5
DNAK
Inverter station
No.
Error
code
Format
Number of characters
1 2 3 4
C
(No data error
detected)
ACK
Inverter station
No.
F
(Data error detected)
NAK
Inverter station
No.