730
APPENDIX
For details, refer to page 359.
Run command
Users can specify the terminal function using this data. These bits function is depending on inverter parameter setting. (Refer to page 430)
<32bit data>
H003E Transistor thermal load factor 0.1% unsigned R
H003F reserved - - -
H0040 PTC thermistor resistance ohm unsigned R
H0041
Output power
(with regenerative display)
R
H0042 Cumulative regenerative power R
H0043 reserved
H0044 2nd PID set point 0.1% unsigned R/W
H0045 2nd PID measured value 0.1% unsigned R/W
H0046 2nd PID deviation 0.1% unsigned R/W
H0048 to
H004F
reserved - - -
H0050 Integrated power on time R
H0051 Running time R
H0052 Saving energy monitor R
H0053 reserved - - -
H0054 Fault code (1) - - R
H0055 Fault code (2) - - R
H0056 Fault code (3) - - R
H0057 Fault code (4) - - R
H0058 Fault code (5) - - R
H0059 Fault code (6) - - R
H005A Fault code (7) - - R
H005B Fault code (8) - - R
H00F9 Run command
--R/W
H00FA to
H01FF
reserved - - -
b15 b0
----RES
STP
(STOP)
CS JOG MRS RT RH RM RL - - AU
No. Description Unit Type
Read/
write
H0200 reserved - - -
H0201 Output frequency (0-15bit)
0.01Hz signed R
H0202 Output frequency (16-31bit)
H0203 Setting frsequency (0-15bit)
0.01Hz signed R
H0204 Setting frequency (16-31bit)
H0205 Motor rotation (0-15bit)
1r/min signed R
H0206 Motor rotation (16-31bit)
H0207 Load meter (0-15bit)
0.1% signed R
H0208 Load meter (16-31bit)
H0209 Positioning pulse (0-15bit)
1signedR/W
H020A Positioning pulse (16-31bit)
H020B Watt-hour meter (1kWh step) (0-15bit)
1kWh unsigned R
H020C Watt-hour meter (1kWh step) (16-31bit)
H020D Watt-hour meter (0.1/0.01kWh step) (0-15bit)
0.1/0.01kWh unsigned R
H020E Watt-hour meter(0.1/0.01kWh step) (16-31bit)
H020F Position error (0-15bit)
1signedR
H0210 Position error (16-31bit)
H0211 to
H03FF
reserved - - -
No. Description Unit Type
Read/
write