EasyManuals Logo

IDEC WindO/I-NV4 User Manual

IDEC WindO/I-NV4
1738 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #1538 background imageLoading...
Page #1538 background image
3 Analog I/O Modules
30-28 WindO/I-NV4 User’s Manual
Mixed Analog I/O Module
Allocation of device address for the mixed analog I/O module is shown below.
For details on the parameter setting values for analog inputs, refer to “ Analog Input Parameter Setting Values” on
page 30-25. For analog outputs, refer to “ Analog Output Parameter Setting Values” on page 30-27.
Channel
Parameter R/W
FC6A-L06A1
FC6A-L06A4
FC6A-L03CN1
FC6A-L03CN4
No. I/O Address Number I/O Address Number
CH0
Analog data R
Input
+0
Input
+0
Analog status R +1 +1
CH1
Analog data R +2 +2
Analog status R +3 +3
CH2
Analog data R +4
Output
+4
Analog status R +5 +5
CH3
Analog data R +6
Analog status R +7
CH4
Analog data R
Output
+8
Analog status R +9
CH5
Analog data R +10
Analog status R +11