WindO/I-NV4 User’s Manual 3-129
7 BACnet Communication
3
Communication
Binary Output Object
This object manages a binary value (on/off). Use this object when the MICRO/I receives binary values from BACnet
devices.
Properties List
(1): Read and write from BACnet devices
(2): Read and write from device addresses when properties are allocated to device addresses
R: Read-only, W: Write-only, R/W: Read and write, -: Not Read and write
*1 Character encoding is ISO 10646 (UTF-8), and the maximum size is 64 bytes.
*2 Cannot be displayed on WindO/I-NV4.
Property Identifier Data Type of Property (1) (2) Comments
Object_Identifier BACnetObjectIdentifier R - Set a fixed value with WindO/I-NV4.
Object_Name
Character string
*1
R - Set a fixed value with WindO/I-NV4.
Object_Type BACnetObjectType R - Set a fixed value with WindO/I-NV4.
Present_Value BACnetBinaryPV R R Refer to “Present_Value” on page 3-132.
Description
Character string
*1
R - Set a fixed value with WindO/I-NV4.
Device_Type
Character string
*1
R - Set a fixed value with WindO/I-NV4.
Status_Flags BACnetStatus_Flags R R Refer to “Status_Flags” on page 3-145.
Event_State BACnetEventState R - Normal (fixed).
Reliability BACnetReliability R R/W
Indicates whether or not the value of
Present_Value is reliable.
Out_Of_Service Logical value R/W R/W Refer to “Out_Of_Service” on page 3-146.
Polarity BACnetPolarity R/W - Refer to “Polarity” on page 3-145.
Priority_Array BACnetPriority_Array R/W - Refer to “Priority_Array” on page 3-145.
Relinquish_Default BACnetBinaryPV R/W - Refer to “Relinquish_Default” on page 3-145.
Property_List
*2
BACnetARRAY[N] of type
BACnetPropertyIdentifier
R - Cannot be edited with WindO/I-NV4.