Example for grounding
Note the following points:
1) The shielding for the CAN-bus connection is grounded on one side.
2) The shielding may not be connected on both sides since ground loops could result otherwise.
3) In order to avoid common mode errors, the signal reference can be connected to imc CANSAS
ground via a resistor.