Parameter List
Parameter list (by parameter number)
PARAMETERS
135
Pr.
List
5
Communication
549 N000
Protocol selection 0, 1 1 0 560
550 D012
NET mode operation command
source selection
0, 1, 9999 1 9999 316
551 D013
PU mode operation command
source selection
1 to 3, 9999 1 9999 316
552 H429
Frequency jump range 0 to 30 Hz, 9999 0.01 Hz 9999 346
PID
control
553 A603
PID deviation limit 0 to 100%, 9999 0.1% 9999 501
554 A604
PID signal operation selection 0 to 3, 10 to 13 1 0 501
Current average
value monitor
555 E720
Current average time 0.1 to 1 s 0.1 s 1 s 283
556 E721
Data output mask time 0 to 20 s 0.1 s 0 s 283
557 E722
Current average value monitor
signal output reference current
0 to 500 A
0.01 A
Rated inverter
current
283
0 to 3600 A
0.1 A
560 A712
Second frequency search gain 0 to 32767, 9999 1 9999 536
561 H020
PTC thermistor protection level 0.5 to 30 k, 9999 0.01 k 9999 331
563 M021
Energization time carrying-over
times
(0 to 65535) 1 0 359
564 M031
Operating time carrying-over times (0 to 65535) 1 0 359
Second
motor
constants
569 G942
Second motor speed control gain 0 to 200%, 9999 0.1% 9999 170
Multiple
rating
570 E301
Multiple rating setting
0 to 3
12 265
1, 2
571 F103
Holding time at a start 0 to 10 s, 9999 0.1 s 9999 298
573
A680
4 mA input check selection 1 to 4, 9999 1 9999 426
T052
574 C211
Second motor online auto tuning 0, 1 1 0 460
PID
control
575 A621
Output interruption detection time 0 to 3600 s, 9999 0.1 s 1 s 501
576 A622
Output interruption detection level 0 to 590 Hz 0.01 Hz 0 Hz 501
577 A623
Output interruption cancel level 900 to 1100% 0.1% 1000% 501
Traverse function
592 A300
Traverse function selection 0 to 2 1 0 484
593 A301
Maximum amplitude amount 0 to 25% 0.1% 10% 484
594 A302
Amplitude compensation amount
during deceleration
0 to 50% 0.1% 10% 484
595 A303
Amplitude compensation amount
during acceleration
0 to 50% 0.1% 10% 484
596 A304
Amplitude acceleration time 0.1 to 3600 s 0.1 s 5 s 484
597 A305
Amplitude deceleration time 0.1 to 3600 s 0.1 s 5 s 484
598 H102
Undervoltage level 350 to 430 V, 9999 0.1 V 9999 341
599 T721
X10 terminal input selection 0, 1 1
0
614
1
Electronic thermal
O/L relay
600 H001
First free thermal reduction
frequency 1
0 to 590 Hz, 9999 0.01 Hz 9999 331
601 H002
First free thermal reduction ratio 1 1 to 100% 1% 100% 331
602 H003
First free thermal reduction
frequency 2
0 to 590 Hz, 9999 0.01 Hz 9999 331
603 H004
First free thermal reduction ratio 2 1 to 100% 1% 100% 331
604 H005
First free thermal reduction
frequency 3
0 to 590 Hz, 9999 0.01 Hz 9999 331
606 T722
Power failure stop external signal
input selection
0, 1 1 1 540
607 H006
Motor permissible load level 110 to 250% 1% 150% 331
Function
Pr.
Pr.
group
Name Setting range
Minimum
setting
increments
Initial value
Refer
to
page
Customer
setting
FM CA