General notes on working with imc CANSAS modules 113
imc CANSAS Users Manual - Doc. Version 1.9 - 05.12.2014© 2014 imc Meßsysteme GmbH
12.You can leave the Reset-plug on the module. Confirm with Yes.
13.Once configuration has been successfully completed, the final prompt to pull out the Reset-plug
appears:
14. Remove the Reset-plug and re-connect the module to the CAN-Bus. For this purpose, the supply
voltage must at least be briefly interrupted so that the module can reboot. Note that this is the
moment to re-attach any terminator plug which may have been removed before. The CAN-Bus
must be connected to 120 at each end.
The Reset-plug is not needed for normal operation. We highly recommend that you always operate all
imc CANSAS-modules, which are used in a single environment, with the same CAN-parameters (i.e. Baud
rate, Master-ID, Slave-ID). Then you can combine any modules to CAN-Busses without their interfering
with each other.
If you use multiple imc CANSAS-modules in conjunction, give regard also to the notes on rack operation.
There you can find hints especially on the topic of running multiple modules.