3.13
Date Code 20170927 Instruction Manual SEL-751 Relay
PC Software
Meter and Control
Meter and Control
Click on Tools > HMI > HMI to bring up the screen shown in Figure 3.12.
The HMI tree view shows all the functions available from the HMI function.
Unlike the self-configuration of the device, the HMI tree remains the same
regardless of the type of cards installed. For example, if no Analog Input card
is installed, the Analog Input function is still available, but the device
responds as follows:
No Analog Input Card Present.
Device Overview
The device overview screen provides an overview of the device. The Contact
I/O portion of the window displays the status of the two inputs and three
outputs of the main board. You cannot change these assignments.
Figure 3.12 Device Overview Screen
You can assign any Relay Word bit to the 16 user-defined target LEDs. To
change the present assignment, double-click on the text above the square you
want to change. After double-clicking on the text, a box with available Relay
Word bits appears in the lower left corner of the screen. Select the appropriate
Relay Word bit, and click the Update button to assign the Relay Word bit to
the LED. To change the color of the LED, click in the square and make your
selection from the color palette.