Date Code 20170927 Instruction Manual SEL-751 Relay
Protection and Logic Functions
Group Settings (SET Command)
q From Table 4.20; w to Figure 4.32 and Figure 4.33; e from Figure 4.24.
Figure 4.28 Channel IN Current-Polarized Directional Element
Forward Threshold = (Channel I
N
Nominal Rating) • (Phase Channels Nominal Rating) • (0.05)
2
Forward Threshold:
Reverse Threshold = —(Channel I
N
Nominal Rating) • (Phase Channels Nominal Rating) • (0.05)
2
Reverse Threshold:
DIRIE is highest
RDIRI
(Reverse)
FDIRI
(Forward)
Best Choice
Ground
Directional
Logic
50GF
Enable
Forward
Threshold
DIRIE
Reverse
Threshold
50GR
Re[I
G
•(I
N
•1∠INMTA)*]
I
G
I
N
Relay
Word
Bits
Relay
Word
Bit
Relay
Word
Bit
Relay
Word
Bit
choice that is asserted
(I
G
= 3I
0
)
(Residual)
3
1
3
3
2
NOTE: Group setting INMTA is hidden
and forced to 0.00 when KGN = OFF.