EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-751 - Figure 4.42 Traditional Channel in Current-Polarized Directional Element

Schweitzer Engineering Laboratories SEL-751
934 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.61
Date Code 20170927 Instruction Manual SEL-751 Relay
Protection and Logic Functions
Group Settings (SET Command)
50GFP—Forward Directional Residual Ground Current Pickup
50GRP—Reverse Directional Residual Ground Current Pickup
If setting ORDER does not contain V or I (no zero-sequence voltage-polarized
or channel IN current-polarized directional elements are enabled), then set-
tings 50GFP and 50GRP are not made or displayed.
The 50GFP setting (3I0 current value) is the pickup for the forward fault
detector 50GF of the zero-sequence voltage-polarized and channel IN current-
polarized directional elements (see Figure 4.24). Ideally, this setting is above
normal load unbalance and below the lowest expected zero-sequence current
magnitude for unbalanced forward faults.
The 50GRP setting (3I0 current value) is the pickup for the reverse fault detec-
tor 50GR of the zero-sequence voltage-polarized and channel IN current-
polarized directional elements (see Figure 4.24). Ideally, this setting is above
normal load unbalance and below the lowest expected zero-sequence current
magnitude for unbalanced reverse faults.
See Petersen Coil Considerations for Setting ORDER on page 4.58 for more
information on setting 50GFP and 50GRP for a Petersen coil-grounded sys-
tem.
50GFP and 50GRP Set Automatically. If enable setting EDIR := AUTO,
settings 50GFP and 50GRP are set automatically at:
50GFP = 0.50 A secondary (5 A nominal phase current inputs, IA, IB, IC)
50GRP = 0.25 A secondary (5 A nominal phase current inputs, IA, IB, IC)
50GFP = 0.10 A secondary (1 A nominal phase current inputs, IA, IB, IC)
50GRP = 0.05 A secondary (1 A nominal phase current inputs, IA, IB, IC)
Operation of the Channel IN Current-Polarized Directional Element
Figure 4.28 shows the logic for the current polarized directional element for
ground faults. Traditional elements of this type use the directional characteris-
tics shown in Figure 4.42, where the maximum torque line of the element is in
phase with the polarizing current, I
N
. This is adequate for solidly-grounded
and most low-impedance grounded systems.
Figure 4.42 Traditional Channel IN Current-Polarized Directional Element
V
A
I
N
Reverse
Forward
I
G
Maximum
Torque
Line

Table of Contents

Related product manuals