Date Code 20170927 Instruction Manual SEL-751 Relay
Firmware, ICD, and Manual Versions
Firmware
Table A.2 R100 Series Firmware Revision History (Sheet 1 of 5)
Firmware Identification (FID) Number Summary of Revisions
Manual
Date Code
SEL-751-R112-V3-Z006002-D20170922 Includes all the functions of SEL-751-R112-V2-Z006002-D20170814
with the following additions:
Addressed an issue in the previous firmware that could cause
IEC 61850 GI buffered reports to be out of sequence when the number
of uncollected reports exceeded 200.
20170922
SEL-751-R112-V2-Z006002-D20170814 Includes all the functions of SEL-751-R112-V1-Z006002-D20160930
with the following additions:
Resolved an issue where certain Ethernet traffic could cause diagnostic
restarts.
NOTE: When upgrading to the R200 series firmware from the R100 series
firmware, make sure to upgrade to firmware version R200-V3 or higher to
maintain the Ethernet traffic resolution of this R100 series firmware point
release.
20170814
SEL-751-R112-V1-Z006002-D20160930 Includes all the functions of SEL-751-R112-V0-Z006002-D20151112
with the following additions:
Resolved a relay disabling issue when the setting EPMU was set to Y
and there was a corrupt IRIG signal.
20160930
Resolved an issue where HIF event reports may not get triggered if
rising-edge triggered Relay Word bits are used in the HIFER setting.
Resolved an issue causing HIF false alarms in the A-phase channel in
the HIF Detection Non-Harmonic Method algorithm.
Modified GOOSE subscription to update data after the messages
transition from lower to better quality.
Resolved an issue where the relay was not allowing access to the
settings using FTP protocol unless the relay part number included the
IEC 61850 protocol option.
SEL-751-R112-V0-Z006002-D20151112
Enhanced the firmware to add directional control capability to support
high-impedance, ungrounded and Petersen coil-grounded systems in
relays with the 200 mA CT option. The 200 mA CT can also be used
for nondirectional sensitive earth fault (SEF) protection.
20151112
Added 8 Vac rms Low-Energy Analog (LEA) ac inputs for system
voltages and synchronism-check input.
Added IEC-60870-5-103 protocol.
Added IEC 62439 Parallel Redundancy Protocol (PRP) for models
with the dual Ethernet port option.
Increased the number of DNP sessions from 3 to 5.
Updated IEC 61850 protocol implementation to IEC 61850 Edition 2.
Added password authentication and session timeout for MMS services.
Enhanced the CPU card design, including the addition of a GOOSE
port with a dedicated MAC address to improve GOOSE processing
performance. (Note: Relays with older CPU cards can be upgraded to
firmware versions R112 or higher, but the relay will not have the
GOOSE performance improvements.)
Added file transfer support in IEC 61850 for CEV events,
COMTRADE events, MET reports, SER reports, BRE reports, CID
files, and Settings file.
Added the inverse-time over- and undervoltage elements.
Added IEC line/cable thermal overload protection elements to protect
the overhead lines and cables against thermal overloads.
Added a vector shift protection function to detect a generator islanding
condition based on the phase shift of the voltage waveform.