EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-751 - Table 4.26 Effect of Settings VSCONN and DELTA_Y on Petersen Coil Directional Elements

Schweitzer Engineering Laboratories SEL-751
934 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.76
SEL-751 Relay Instruction Manual Date Code 20170927
Protection and Logic Functions
Group Settings (SET Command)
These details are important in relay testing, when the signal applied to the VS-
NS terminals represents a 3V
0
zero-sequence voltage signal, and
VSCONN := 3V0. When making test settings or interpreting test results,
remember that the relay scales the measured value by PTRS/PTR before using
it in the Petersen coil directional element and in the various zero-sequence
voltage-polarized directional elements.
EDIRIV—SELOGIC Control Equation Enable
Refer to Figure 4.24 and Figure 4.25.
SEL
OGIC control equation setting EDIRIV must be asserted to logical 1 to
enable the zero-sequence voltage-polarized and channel IN current-polarized
directional elements for directional control of neutral ground and residual
ground overcurrent elements.
For most applications, set EDIRIV directly to logical 1:
EDIRIV = 1 (numeral 1)
For situations where zero-sequence source isolation can occur (e.g., by open-
ing a circuit breaker) and result in possible mutual coupling problems for the
zero-sequence voltage-polarized and channel IN current-polarized directional
elements, SEL
OGIC control equation setting EDIRIV should be deasserted to
logical 0. In this example, connect a circuit breaker auxiliary contact from the
isolating circuit breaker to the SEL-751:
EDIRIV = IN102 (52a connected to optoisolated input IN102)
Almost any desired control can be set in SEL
OGIC control equation setting
EDIRIV.
Ungrounded/High-Impedance Grounded System Considerations for
Setting EDIRIV
On ungrounded/high-impedance grounded systems (when setting
ORDER := U), phase-to-phase or unbalanced three-phase faults can cause the
ungrounded/high-impedance grounded element to operate on false quantities.
To prevent this situation, SEL
OGIC setting EDIRIV may be used as follows:
EDIRIV := V1GOOD * !DIRQE
The V1GOOD Relay Word bit (V1GOOD asserts if the positive sequence
voltage is greater than 75%*VNOM/sqrt(3) and deasserts during a three-phase
fault, and the DIRQE Relay Word bit (see Figure 4.23) asserts during a phase-
to-phase fault. If either one of these occur, the EDIRIV setting evaluates to
logical 0, and the ungrounded/high-impedance grounded directional element
is blocked (see Figure 4.25).
Table 4.26 Effect of Settings VSCONN and DELTA_Y on Petersen Coil Directional Elements
Relay Function
When VSCONN := VS and
DELTA_Y := WYE
When VSCONN := VS and
DELTA_Y := DELTA
When VSCONN := 3V0
(DELTA_Y := WYE or DELTA,
and SINGLEV := Y)
Wattmetric and incremental
conductance elements
(ORDER setting choice “P”).
Use 3V0 calculated from V
A
,
V
B
, V
C
as polarizing voltage.
ORDER cannot be set to con-
tain “P” (no zero-sequence
voltage source is available)
Use V
S
• (PTRS/PTR) as 3V0
polarizing voltage.
a
a
The PTRS/PTR adjustment brings the broken-delta 3V0 quantity to the same base voltage as the relay settings 59RES, DIRWFP, and
DIRWRP, which are based on the VA, VB, VC voltage base.

Table of Contents

Related product manuals