EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-751 - Figure 4.50 Zero-Sequence Impedance Plots for Ground Fault on Low-Impedance Grounded Distribution System

Schweitzer Engineering Laboratories SEL-751
934 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.68
SEL-751 Relay Instruction Manual Date Code 20170927
Protection and Logic Functions
Group Settings (SET Command)
The zero-sequence voltage/current vector values of Figure 4.49 are converted
(using polarity and impedances in Figure 4.47) to the apparent zero-sequence
impedances that the respective relays see, as plotted in Figure 4.50:
Ground fault on Feeder 1 is in the forward direction for
Relay 1:
V
0
/(–I
0(1)
) = parallel combination of zero-sequence impedance
valuesjXC
0(2)
, –jXC
0(n)
, and 3R
G
+ Z
0T
V
0
/I
0(1)
= –(parallel combination of zero-sequence impedance
valuesjXC
0(2)
, –jXC
0(n)
, and 3R
G
+Z
0T
)
V
0
/I
0(1)
= the negative value of the aggregate zero-sequence
impedance behind Relay 1
Ground fault on Feeder 1 is in the reverse direction for Relay 2:
V
0
/I
0(2)
= –jXC
0(2)
V
0
/I
0(2)
= the zero-sequence capacitive reactance for Feeder 2
in front of Relay 2
Figure 4.50 Zero-Sequence Impedance Plots for Ground Fault on Low-
Impedance Grounded Distribution System
Presuming that all of the feeders in this distribution substation example have
roughly the same amount of capacitance-creating network (e.g., underground
cable), then the following applies:
The Relay 1 apparent zero-sequence impedance plot in
Figure 4.50 is representative of a ground fault in front of any
relay in the substation (forward fault).
The Relay 2 apparent zero-sequence impedance plot in
Figure 4.50 is representative of a ground fault behind any relay
in the substation (e.g., a ground fault on another parallel feeder;
reverse fault).
The forward/reverse impedance plots in Figure 4.50 appear asymmetric, espe-
cially when compared to Figure 4.45(a) for a solidly grounded system with
sources at each end. The Z0MTA setting in Figure 4.45(a) would (by inspec-
tion) be approximately 75 degrees.
Contrastingly, the Z0MTA setting for Figure 4.50 has to allow the forward/
reverse characteristic to fit in between the forward/reverse impedance plots.
The forward impedance plot is the most critical to accommodate—one defi-
R
0
jX
0
—jX
0
Relay 2
(reverse fault)
Relay 1
(forward fault)
—R
0
Decreasing R
G

Table of Contents

Related product manuals