EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-751 - Table 4.43 Voltages When Setting SINGLEV:= y; Table 4.44 Power Element Settings

Schweitzer Engineering Laboratories SEL-751
934 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.115
Date Code 20170927 Instruction Manual SEL-751 Relay
Protection and Logic Functions
Group Settings (SET Command)
Set 25ANG2 = 25° and use the resultant synchronism-check element in man-
ual close logic to supervise manual closing (for example, assert IN301 to initi-
ate manual close), e.g.,
CL := IN301 AND (25A2 OR …) (see Figure 4.80)
In this example, the angular difference across the circuit breaker can be
greater for a manual close (25 degrees) than for an automatic reclose
(15 degrees).
A single output contact (e.g., OUT102 := CLOSE) can provide the close func-
tion for both automatic reclosing and manual closing (see Figure 4.80 for
logic output).
Power Elements
You can enable as many as two independent three-phase power elements in the
SEL-751. Each enabled element can be set to detect real power or reactive
power. When voltage inputs to the relay are from delta-connected PTs or when
you use a single voltage input, the relay cannot account for unbalance in the
voltages in calculating the power. When you use one voltage (only the VA or
VAB) and set SINGLEV := Y, the relay assumes that the system voltages are
balanced in both magnitude and phase angle. Power and power factor are cal-
culated assuming balanced voltages. Take this into consideration in applying
the power elements.
With SEL
OGIC control equations, the power elements provide a wide variety
of protection and control applications. Typical applications are:
Overpower and/or underpower protection/control
Reverse power protection/control
VAR control for capacitor banks
Table 4.43 Voltages When Setting SINGLEV := Y
DELTA_Y Setting PHROT Setting Voltages
WYE ABC VA = |Va| °
VB = |Va| –120°
VC = |Va| +120°
WYE ACB VA = |Va| 
VB = |Va| +120
VC = |Va| –120
DELTA ABC VAB = |Vab| 
VBC = |Vab| –120
VCA = |Vab| +120
DELTA ACB VAB = |Vab| 
VBC = |Vab| +120
VCA = |Vab| –120
Table 4.44 Power Element Settings (Sheet 1 of 2)
Setting Prompt Setting Range
Setting Name :=
Fac to ry Defa ult
ENABLE PWR ELEM N, 3P1, 3P2 EPWR := N
3PH PWR ELEM PU OFF, 1.0–6500.0 VA
a
(sec-
ondary)
3PWR1P := OFF
PWR ELEM TYPE +WATTS, –WATTS,
+VARS, –VARS
PWR1T := +VARS

Table of Contents

Related product manuals