D.29
Date Code 20170927 Instruction Manual SEL-751 Relay
DNP3 Communications
DNP3 Documentation
You can also use ACSELERATOR QuickSet to enter the AO map settings as
shown in the screen capture in Figure D.9.
Figure D.9 Analog Output Map Entry in ACSELERATOR QuickSet Software
The SET DNP x CO_00 <Enter> command allows you to populate the DNP
counter map with per-point dead bands. Entering these settings is similar to
defining the analog input map settings.
You can use the command SET DNP x BO_00 TERSE <Enter> to change
the binary output map x as shown in Figure D.10. You can populate the
custom BO map with any of the 32 remote bits (RB01–RB32). You can define
bit pairs in BO maps by including a colon (:) between the bit labels.
=>>SET DNP 1 AO_00 TERSE <Enter>
DNP Map 1 Settings
Analog Output Map
DNP Analog Output Label Name (6 characters) AO_00 := NA ? group
DNP Analog Output Label Name (6 characters) AO_01 := NA ? ra001
DNP Analog Output Label Name (6 characters) AO_02 := NA ? ra002
DNP Analog Output Label Name (6 characters) AO_03 := NA ? ra120
DNP Analog Output Label Name (6 characters) AO_04 := NA ? ra128
DNP Analog Output Label Name (6 characters) AO_05 := NA ?
DNP Analog Output Label Name (6 characters) AO_06 := NA ? end
Save changes (Y,N)? y
Settings Saved
=>>
Figure D.8 Sample Custom DNP3 AO Map Settings