EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-751 - Table 4.97 Example Settings and Displays; Table 4.96 Entry in the Name String and the Alias Strings; Figure 4.120 Front-Panel Display for an Entry in (A) Boolean Name and Alias Strings and (B) Analog Name and User Text and Formatting Strings; Figure 4.121 Front-Panel Display for an Entry in (A) Boolean Name and Alias Strings and (B) Analog Name, User Text and Formatting Strings, and Engineering Units

Schweitzer Engineering Laboratories SEL-751
934 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.200
SEL-751 Relay Instruction Manual Date Code 20170927
Protection and Logic Functions
Front-Panel Settings (SET F Command)
Figure 4.120 shows the front-panel display for the entry in Table 4.96. Input
IN101 is deasserted in this display (0), and the display changes to
INPUT
IN101=1
when Input IN101 asserts.
Figure 4.120 Front-Panel Display for an Entry in (a) Boolean Name and Alias
Strings and (b)AnalogNameandUserTextandFormattingStrings
If the engineering units are set, then the front-panel display shows the engi-
neering units. For example, in the Group setting example, we set AI301EU to
degrees C. With this setting, the front-panel display looks as shown in
Figure 4.121.
Figure 4.121 Front-Panel Display for an Entry in (a) Boolean Name and Alias
Strings and (b) Analog Name, User Text and Formatting Strings,
and Engineering Units
For fixed text, enter a 1 in the Name String, then enter the fixed text as the
alias text. For example, to display the word DEFAULT and SETTINGS on two
different lines, use a display point for each word, i.e., DP01 = 1,“DEFAULT”
and DP02 = 1,“SETTINGS.Table 4.97 shows other options and front-panel
displays for the User Text and Formatting settings.
Following is an example of an application of analog settings. Assume we also
want to know the hot-spot temperature, oil temperature, and winding tempera-
ture of the transformer at a certain installation. To measure these temperatures,
Table 4.96 Entry in the Name String and the Alias Strings
Name Alias Set String Clear String
IN101 INPUT IN101
AI301 TEMPERATURE
Table 4.97 Example Settings and Displays
Example Display Point Setting Value Example Display
AI301,"TEMP {4} deg C" TEMP 1234 deg C
AI301,"TEMP = {4.1}" TEMP := xx.x
AI301,"TEMP = {5}" TEMP := 1230
AI301,"TEMP = {4.2,0.001} C" TEMP := 1.23 C
AI301,"TEMP HV HS1 = {4,1000}" TEMP HV HS1 =1234
1,{} Empty line
1,“Fixed Text” Fixed Text
0 Hides the display point
INPUT IN101:=0
TEMPERATURE:
0.024 mA
(a) Boolean
(b) Analog
INPUT IN101:=0
TEMPERATURE:
0.024 degree C
(a) Boolean
(b) Analog

Table of Contents

Related product manuals