EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-751 - Figure 7.33 CFG.TXT File; Table 7.56 FTP and MMS Virtual File Structure

Schweitzer Engineering Laboratories SEL-751
934 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.58
SEL-751 Relay Instruction Manual Date Code 20170927
Communications
Communications Protocols
Virtual File Interface
You can retrieve and send data as files through the relay virtual file interface.
Devices with embedded computers can also use the virtual file interface.
Send and receive files using the following three protocols:
FTP and MMS File Structure
The Ethernet File Transfer Protocol (FTP) and the IEC-61850 Manufacturing
Messaging Specification (MMS) have a two-level file structure. Files are
available at the root level and subdirectories. Tabl e 7 .5 6 shows the directories
and their contents.
Root Directory
The root directory (/) contains files and subdirectories as shown in Table 7.56.
CFG.TXT File (Read-Only). The CFG.TXT file contains general
configuration information about the relay and each settings class. External
support software retrieves the CFG.TXT file to interact automatically with the
relay. Calibration settings are included only when the file is read at Access
Level C.
1. File Transfer Protocol (FTP)- Ethernet Port only
2. MMS File Transfer - Ethernet Port only
3. Ymodem - Serial or Ethernet Ports
Table 7.56 FTP and MMS Virtual File Structure
Directory Contents
/ (Root) CFG.TXT
a
file, CFG.XML file, ERR.TXT file and
SET_61850.CID and the SETTINGS, REPORTS, EVENTS,
COMTRADE
b
, and HMI directories
/SETTINGS
a
a
Only available in FTP file structure.
Relay settings
/REPORTS SER, LDP, circuit breaker, and history reports
/EVENTS CEV, COMTRADE, HIF, and history reports
/COMTRADE
b
b
The COMTRADE directory is only available in MMS file structure.
COMTRADE events
/HMI
c
c
Available only in the SEL-751 touchscreen display model.
Touchscreen settings (SET_HMI.zds and CDP.zds) and diagnostics
(HMI_ALL.zip)
[INFO]
RELAYTYPE=SEL-751
FID=SEL-751-X308P-V0-Z006002-D20151111
BFID=
PARTNO=7515010BC6C0C86087X
[CLASSES]
PF,"Port F"
P3,"Port 3"
P1,"Port 1"
G,"Global"
1,"Group 1"
2,"Group 2"
3,"Group 3"
4,"Group 4"
C,"Class C"
L1,"Logic 1"
L2,"Logic 2"
L3,"Logic 3"
L4,"Logic 4"
Figure 7.33 CFG.TXT File (Sheet 1 of 2)

Table of Contents

Related product manuals