Date Code 20170927 Instruction Manual SEL-751 Relay
SET.1
of 78
SEL-751 Settings Sheets Date__________
Group Settings (SET Command) Identifier
SEL-751 Settings Sheets
Instruction Manual
These settings sheets include the definition and input range for each setting in the relay. You can access the
settings from the relay front panel and the serial ports. See Section 4: Protection and Logic Functions for
detailed descriptions of the settings.
Some settings require an optional module. Refer to the SEL-751 Model Option Table, and the notes to
the following settings for details on which settings are available in a specific model.
ACSELERATOR
QuickSet SEL-5030 Software, which shows and hides settings depending on the MOT part number
selected, is the best way to view settings available in a specific model.
Some of the settings ranges may be more restrictive than shown, because of settings interdependency
checks performed when new settings are saved.
The settings are not case sensitive.
Group Settings (SET Command)
Identifier
Configuration
Line Parameters
(Hidden if VNOM := OFF)
UNIT ID LINE 1 (16 Characters) RID :=
UNIT ID LINE 2 (16 Characters) TID :=
PHASE CT RATIO (15000) CTR :=
NEUTRAL CT RATIO (1–5000) CTRN :=
PHASE PT RATIO (1.00–10000.00) (Shown if Slot Z = 8x) PTR :=
PHASE LEA RATIO (37.50–500000.00) (Shown if Slot Z = Lx) LEA_R :=
PHASE LEA SCALE (1.00–13333.33 [autocalculated]) (Shown if Slot Z = Lx) LEA_SC :=
SYNCV PT RATIO (1.00–10000.00) (Shown if Slot E = 70) PTRS :=
SYNCV LEA RATIO (37.50–500000.00) (Shown if Slot E = L0) LEA_S_R :=
SYNCV LEA SCALE (1.00–13333.33 [autocalculated]) (Shown if Slot E = L0) LEA_S_SC :=
XFMR CONNECTION (WYE, DELTA) (Hidden if Slot Z = Ax) DELTA_ Y :=
VS CONNECTION (VS, 3V0) (Shown if Slot E = 70 or L0) VSCONN :=
SINGLE V INPUT (Y, N) (Hidden if Slot Z = Ax) SINGLEV :=
LINE VOLTAGE (OFF, 20.00–250.00 V{if DELTA_Y := DELTA}, OFF,
20.00–480.00 V{if DELTA_Y:= WYE}) (Hidden and set to OFF when Slot Z = Ax
or SINGLEV = Y) VNOM :=
POS SQ LN Z MAG (0.10–510.00 ohm {5 A nom},
(0.50–2550.00 ohm {1 A nom}) Z1MAG :=
POS SQ LN Z ANG (5.00–90.00 deg) Z1ANG :=
ZERO SQ LN Z MAG (0.10–510.00 ohm {5 A nom},
(0.50–2550.00 ohm {1 A nom}) Z0MAG :=
ZERO SQ LN Z ANG (5.00–90.00 deg) Z0ANG :=