F.51
Date Code 20170927 Instruction Manual SEL-751 Relay
IEC 61850 Communications
ACSI Conformance Statements
Generic Substation Event Model (GSE) (Clause 14.3.5.3.4)
GOOSE-Control-Block
S35 SendGOOSEMessage MC c8
e
c8
e
YES
S36 GetReference TP O
b
c9
f
S37 GetGOOSEElement
Number TP O
b
c9
f
S38 GetGoCBValues TP O
b
O
b
YES
S39 SetGoCBValues TP O
b
O
b
ONLY
GSSE-Control-Block
S40 SendGSSEMessage MC c8
e
c8
e
S41 GetReference TP O
b
c9
f
S42 GetGSSEElement
Number TP Ob c9
f
S43 GetGsCBValues TP O
b
O
b
S44 GetGsCBValues TP O
b
O
b
Transmission of Sample Value Model (SVC) (Clause 16)
Multicast SVC
S45 SendMSVMessage MC c10
g
c10
g
S46 GetMSVCBValues TP O
b
O
b
S47 SetMSVCBValues TP O
b
O
b
Unicast SVC
S48 SendUSVMessage MC c10
g
c10
g
S49 GetUSVCBValues TP O
b
O
b
S50 SetUSVCBValues TP O
b
O
b
Control (Clause 16.4.8)
S51 Select M
a
O
b
S52 SelectWithValue TP Ma O
b
YES
S53 Cancel TP O
b
M
a
YES
S54 Operate TP M
a
M
a
YES
S55 Command-Termination TP M
a
M
a
YES
S56 TimeActivated-Operate TP O
b
O
b
File Transfer (Clause 20)
S57 GetFile TP O
b
M
a
S58 SetFile TP O
b
O
b
S59 DeleteFile TP O
b
O
b
S60 GetFileAttributeValues TP O
b
M
a
Time (Clause 5.5)
T1 Time resolution of internal
clock (nearest negative
power of 2 in seconds)
20 (1 µs)
T2 Time accuracy of internal
clock
7 (10 ms) for SNTP
18 (4 µs) for IRIG-B
T1 YES (for IRIG-B)