I.19
Date Code 20170927 Instruction Manual SEL-751 Relay
Synchrophasors
IEEE C37.118 PMU Setting Example
The SEL-751 does not begin transmitting synchrophasors until an enable
message is received from the synchrophasor processor. The relay stops
synchrophasor transmission when the appropriate command is received from
the synchrophasor processor. The SEL-751 can also indicate when a
configuration change occurs, so the synchrophasor processor can request a
new configuration block and keep its database up-to-date.
The SEL-751 only responds to configuration block request messages when it
is in the non-transmitting mode.