SAW sensor – Parameter
Type 8098 FLOWave L
15.4.4 Deactivating the damping of the volume ow rate values

Go to the CONFIGURATION view.
SAWsensor
Parameter view.
Stand.meas.values
Volumeow .
Damping The Currentsettings are displayed
None The Newsettings are displayed.


15.4.5 Activating the monitoring of the volume ow rate

value can be too high or too low.
A monitored value can be:
in the normal operating range.
in the warning range,
in the error range.
You can set 4 limit values: 2 error limits and 2 warning limits.

.

the normal range into the warning range). The reaction time depends on the hysteresis value and whether
the monitored value increases or decreases.