Maintenance and troubleshooting
Type 8098 FLOWave L
24.9.11 Message "Internal message store overow"
Message

Symboldisplayedinthe
informationbar
Possiblecause The number of messages generated by the device is higher than the
memory capacity.
Whattodo?

correct.
24.9.12 Message "No signals from interdigital transducer"
Message
No signals from interdigital transducer
Symboldisplayedinthe
informationbar
-
Possiblecause The sensor is not operating correctly.
Whattodo?
Send the complete device back to Bürkert because the sensor must be
replaced.
24.9.13 Message "No temperature sensor detected"
Message
No temperature sensor detected
Symboldisplayedinthe
informationbar
Possiblecause The temperature of the liquid can neither be measured nor compensated.
Whattodo?
If the temperature of the liquid must be measured, send the complete
device back to Bürkert because the sensor must be replaced.
24.9.14 Message "Pipe characteristics have changed: check limits
values"
Message
Pipe characteristics have changed: check limits values
Symboldisplayedinthe
informationbar
(symbol changed)
Possiblecause The transmitter has been associated with another sensor.
Whattodo? 
correct.