221
SAW sensor – Parameter
Type 8098 FLOWave L
→ Active
→ No.
→
The monitoring of the DF is inactive.
15.12.8 Changing the error limits, the warning limits and the hysteresis
of the dierentiation factor
A monitored value can be:
• in the normal operating range.
• in the warning range,
• in the error range.
You can set 4 limit values: 2 error limits and 2 warning limits.
→ -
.
in
and if the monitored value increases or decreases.
By default, the monitoring of the DF and the diagnostics are all disabled.
To change the error limits, the warning limits and the hysteresis of the DF, do the following:
→ Go to the CONFIGURATION view.
→ SAWsensor
→ Parameter view.
→ Add.meas.values
→ DF
→ Limits
→ Settings The Currentsettings are displayed
→
→
→
→
→ The Newsettings are displayed.
→
The limit values and the hysteresis value are changed.
English