SAW sensor – Parameter
Type 8098 FLOWave L
Countingdirection .


The counting direction is changed.
15.10.3 Activating the monitoring of each volume totalizer value
A monitored value can be:
in the normal operating range.
in the warning range,
in the error range.
You can set 4 limit values: 2 error limits and 2 warning limits.
-
teresis of each volume totalizer.
 in 

and if the monitored value increases or decreases.
By default, the monitoring of the volume totalizers and the diagnostics are all disabled.
To activate the monitoring of each volume totalizer, do the following:
Go to the CONFIGURATION view.
SAWsensor
Parameter view.
Stand.meas.values Totalizer1 or Totalizer2
Limits
Active
Yes

The monitoring of the volume totalizer is active and the device status will change depending on the limits
that have been set.

.

.
To enable the monitoring, i.e. to be informed when the value of a volume totalizer is outside the normal
.
English