EasyManua.ls Logo

Burkert FLOWave L - Activating the Monitoring of the Mass Flow Rate; Deactivating the Damping of the Mass Flow Rate Values

Burkert FLOWave L
354 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
166
SAW sensor – Parameter
Type 8098 FLOWave L
15.5.4 Deactivating the damping of the mass ow rate values

Go to the CONFIGURATION view.
SAWsensor
Parameter view.
Stand.meas.values
Massow .
Damping The Currentsettings are displayed
None The Newsettings are displayed.


15.5.5 Activating the monitoring of the mass ow rate

can be too high or too low.
A monitored value can be:
in the normal operating range.
in the warning range,
in the error range.
You can set 4 limit values: 2 error limits and 2 warning limits.

.

the normal range into the warning range). The reaction time depends on the hysteresis value and whether
the monitored value increases or decreases.
English

Table of Contents

Related product manuals