SAW sensor – Parameter
Type 8098 FLOWave L
15.10.8 Disabling the user to start, stop or reset each volume totalizer
By default, the user is not allowed to start, to stop or to reset a volume totalizer.
If the Start/Stop/Reset of a volume totalizer is active, do the following to disable them:
→ Go to the CONFIGURATION view.
→ SAWsensor
→ Parameter view.
→ Stand.meas.values Totalizer1 or Totalizer2
→ Start/Stop/Reset
→ Disabled
→
The user is not authorized to start or to stop or to reset a volume totalizer.
15.10.9 Starting each volume totalizer
If the Start/Stop/Reset of a volume totalizer is active, do the following to start the volume totalizer:
→ Go to the CONFIGURATION view.
→ SAWsensor
→ Parameter view.
→ Stand.meas.values Totalizer1 or Totalizer2
→ Start/Stop
→ Started
→
The volume totalizer starts to count.
15.10.10 Stopping each volume totalizer
If the Start/Stop/Reset of a volume totalizer is active, do the following to stop the volume totalizer:
→ Go to the CONFIGURATION view.
→ SAWsensor
→ Parameter view.
→ Stand.meas.values Totalizer1 or Totalizer2
→ Start/Stop
→ Stopped
→
The volume totalizer stops counting.